CHW Pump Head Calculator

Pump head along the index circuit of a closed chilled water loop: pipe friction (Darcy–Colebrook) + fittings and valves (Carrier equivalent lengths or ASHRAE K-factors) + equipment from data sheets. Choose the detailed node-by-node method or the quick section method.

Design settings

Detailed method

One row per pipe run, fitting, valve or piece of equipment along the index circuit, from the pump discharge round to the pump suction. Pipe rows: pick the size and enter flow and length. Fittings take the row's size and flow; quantity goes in Length / Qty. Equipment: enter the pressure drop from the data sheet.

Override: your own Le (m) or K for a fitting, depending on the method, or the data-sheet kPa for equipment.

Design basis

Methods behind every number on this page. The same text is printed in the PDF report.

Water and pipe friction

Water properties at the mean CHW temperature (default 5.5 / 14.4 °C): density by the Thiesen equation, viscosity by the Vogel equation.

Velocity from the actual internal diameter of the chosen pipe (default steel Schedule 40). Darcy–Weisbach ΔP/L = (f/D)·ρV²/2 with the Colebrook friction factor, Re = ρVD/μ.

ASHRAE limits (Fundamentals, Pipe Sizing): velocity ≤ 1.2 m/s for 2 in (DN50) and smaller; friction ≤ 400 Pa/m above.

Fittings and valves

Equivalent length (default): Carrier System Design Manual, Part 3 – Piping Design, Table 10 (valves), Table 11 (fittings) and Table 12 (sudden enlargement / contraction, at the smaller size). ΔP = Le × friction rate of the row's pipe.

K-factor: ASHRAE pipe fitting tables (Hydraulic Institute data), screwed up to 2 in, flanged / welded above. ΔP = K·ρV²/2. Items missing from one table use the other, converted with K = f·Le/D; the row says so.

Equipment and total

Chiller evaporator, coils, control valves, balancing valves and heat exchangers from manufacturer data (typical values shown until entered).

Pump head = (pipe + fittings + equipment) × (1 + safety factor). Closed loop: static height is not added. Head in m = ΔP ÷ (ρ·g). Shaft power = Q × ΔP ÷ η.